This sample demonstrates Deliverable #1 - the interactive online report you'll receive after uploading your drawings. Browse detected issues, use AI chat for questions, filter by severity, and track resolution progress with your team.
Community Youth Centre • 3-Storey Mixed Use
Community Youth Centre • 3-Storey Mixed Use Building
Ground floor plan reviewed with full Building Regulations compliance check
11 issues detected across coordination, compliance, and specification
£47,330 in construction rework costs avoided
3h 52m saved vs manual review (97% faster)
Total issue count organized by severity (11 issues detected)
Architects typically spend 4 hours manually checking drawings for these same issues
Browse and filter all issues detected in your drawings. Use AI features to prioritize and resolve efficiently.
Fix these critical and high-priority items immediately to avoid costly delays
When you export your reports, your original drawings return with color-coded issue markers – not just red lines, but a smart red/orange/yellow/green severity system. See critical issues instantly. Share with contractors, import to CAD, or mark up in meetings.
Community Youth Centre — Ground Floor Plan

Hover over any numbered marker on the drawing to see it highlight, then click to instantly jump to the full issue details below. Included in all plans.
Download as PDF, share with contractors, or import markup data back into Revit/AutoCAD for quick fixes.
AI marks exact locations on your drawings - no more hunting through sheets to find where issues are.
Every marker ID links to the interactive report above - see the full analysis, cost impact, and fix template instantly.
Partition wall between Kitchen G.03 and Dining Room G.04 shows no fire rating specification. Part B requires 30-minute fire resistance for commercial kitchen separations.
FIRE-RATED PARTITION SPECIFICATION: Wall Type: FP-01 (Fire Partition 30min) Location: Between Kitchen G.03 and Dining G.04 Construction: • 100mm metal stud framework at 600mm centres • 2 layers 12.5mm fire-rated plasterboard each side • Joints staggered min. 600mm • Acoustic insulation: 100mm mineral wool (optional) • Fire stopping at wall/ceiling junction • Compliance: 30min fire resistance to BS 476-22

High-level section showing non-combustible mineral wool insulation, DPC lead tray, weep holes, and fire separation requirements for masonry construction adjacent to combustible materials. Minimum clearances and fire isolation specification included.
Partition wall between Rooms G.06 and G.08 shows no wall type reference. Drawing key shows types WP-01 to WP-05 but this wall is unlabelled.
WALL TYPE ANNOTATION: Missing wall type: Partition between G.06 and G.08 Recommended annotation: WP-02 • 100mm metal stud partition • Single layer 12.5mm plasterboard each side • 50mm acoustic insulation (Rw 40dB) Add to plan: • Wall type label "WP-02" at mid-span • Reference to wall types legend • Verify specification matches room acoustic requirements

Fully annotated cavity wall plan detail showing 102.5mm facing brickwork, 150mm mineral wool insulation, 100mm blockwork, cavity closer, air tightness tape, and MDF cill. Use as reference for wall type specification and annotation.
Proposed glazed bay window at south elevation (Grid E4, Reference GB-01) has no accompanying detail drawing showing cavity wall abutment, DPC cavity tray, structural steel support, or U-value compliance. Building Control will require this information before approval.
GLAZED BAY WINDOW ABUTMENT DETAIL — GB-01: Required drawings/information: • Detail A: Structural silicone glass-to-glass joint • Cross Section A-A: Full roof-to-wall abutment Specification notes to include: • Lead apron flashing or rigid metal equivalent • DPC cavity tray — turned down on four sides with weep holes • Cavity insulation: continuous through junction (no cold bridge) • Structural support: UC steel beam to Structural Engineer's spec • Glazing: U-value ≤1.4 W/m²K to BS6399 Wind & Snow loading • Floor transom: anodised aluminium to manufacturer's spec • Perimeter floor insulation: 30mm rigid, sealed to airtight membrane • Thermabridge connector plate at cold bridge locations Coordinate with: • Structural Engineer (beam size, wall support above) • Glazing manufacturer (transom spec, silicon joint detail) • Building Control (U-value evidence / SAP calculation update)

Complete abutment detail including Detail A (structural silicone glass-to-glass joint), DPC cavity tray, lead apron flashing, insulated floor transom, Thermabridge connector plate, and Cross Section A-A showing full roof-to-wall construction with U-value compliance notes.
Main escape corridor between Grids B-C measures 1050mm width. Part B requires minimum 1200mm for corridors serving more than 60 persons.
ESCAPE CORRIDOR WIDTH COMPLIANCE: • Current width: 1050mm (non-compliant) • Required width: 1200mm minimum (>60 persons) • Proposed solution: Shift partition wall at Grid B by 150mm north • Impact: Room G.05 reduces from 4.2m to 4.05m (acceptable) • Clear width maintained along entire corridor length • Verify all door swings do not encroach into required width • Update fire strategy drawing to reflect changes
Door D-108 from Store Room G.12 opens outward into protected escape corridor, reducing effective corridor width below 1200mm when open.
FIRE DOOR SWING CORRECTION - D-108: • Current: Door opens outward into corridor (non-compliant) • Required: Door must open into room (away from escape route) • Update door schedule: D-108 swing direction reversed • Verify room clearances: - 300mm clear space beside door when open - No obstruction from shelving/equipment • Update ironmongery schedule (hinges, closer position) • Coordinate with fire strategy consultant • Apply check to all doors opening onto protected corridors
Accessible WC (Room G.14) shows 1400mm x 1800mm clear space. Part M requires minimum 1500mm x 2000mm for wheelchair turning.
ACCESSIBLE WC COMPLIANCE - ROOM G.14: • Clear floor space: Minimum 1500mm x 2000mm (currently 1400mm x 1800mm) • Revise walls to achieve compliant dimensions • Relocate hand basin to side wall (maintain 400mm clearance from corner) • Door swing: Verify 300mm clear space beside door opening • Transfer space: Ensure 1100mm alongside WC pan • Grabrails: Confirm positions per Diagram 2.6, Part M
Door D-102 to Meeting Room G.07 swings inward, clashing with fixed credenza unit shown on furniture layout at 450mm from door frame.
COORDINATION NOTE - DOOR/FURNITURE CLASH: Room G.07, Door D-102 / Credenza Unit Option A (Preferred): Relocate credenza 450mm east • Minimum 900mm clearance from door swing • Maintains door opening inward (quieter for meeting room) • Credenza remains on same wall Option B: Reverse door swing to open outward • Furniture position unchanged • Check corridor width remains >1200mm • Update door schedule D-102 and ironmongery • Consider acoustic impact (door opening into corridor)
Rooms at Grid E2, E3, and F1 show no room numbers or names. All spaces require clear identification for construction and fit-out coordination.
ROOM LABELLING UPDATE: Missing room labels to be added: Grid E2: G.15 - STORE (8.5m²) • Update room schedule with area • Add to door schedule (Door D-115) Grid E3: G.16 - SERVER ROOM (12.2m²) • Update room schedule with area • Specify cooling requirements note • Add to door schedule (Door D-116) Grid F1: G.17 - CLEANERS CUPBOARD (3.8m²) • Update room schedule with area • Add to door schedule (Door D-117)
Door D-105 shown as FD30S fire door in door schedule, but floor plan shows standard door symbol with no fire rating indication.
DOOR SCHEDULE COORDINATION - D-105: Current Discrepancy: • Door Schedule: FD30S fire door • Floor Plan: Standard door symbol (no fire indication) Resolution Required: 1. Verify fire strategy: Is FD30S required for Room G.09? 2. If YES: Update plan symbol to fire door (double line, "FD" label) 3. If NO: Update schedule to standard door type Fire Door Symbol Standards: • Double line on plan (3mm apart) • Label "FD30S" adjacent to door • Self-closing device indication (diagonal line)
External access ramp at main entrance shows 1:10 gradient. Part M requires maximum 1:12 gradient for wheelchair access ramps.
ACCESSIBLE RAMP COMPLIANCE: Current: 1:10 gradient (non-compliant) Required: 1:12 maximum gradient Level change: 250mm Current length: 2.5m Required length: 3.0m (250mm ÷ 12 = 3.0m minimum) Updates Required: • Extend ramp length by 500mm • Handrails both sides: 900-1000mm high • Landings: Min 1500mm x 1500mm at top/bottom • Surface: Non-slip finish, max 5mm upstands • Colour contrast: Nosing and handrail ends
Floor finish schedule shows no specification for Rooms G.11 (IT Room) and G.13 (Comms Room). All rooms require defined floor finishes.
FLOOR FINISH SPECIFICATION: Rooms G.11 (IT Room) & G.13 (Comms Room): Specified Finish: FF-04 • Raised access floor system • Floor depth: 150mm (for cable management) • Surface: Heavy duty carpet tiles • Load rating: Medium duty (3.0 kN/m²) • Fire rating: Class 1 surface spread of flame Installation Notes: • Coordinate with electrical for underfloor power/data • Perimeter closure strips required • Access panels at grid intersections
Issues grouped by category and theme (same 11 issues, organized differently)
Location-based distribution showing where issues are found on site (same 11 issues, by location)
You have 3 fire safety issues clustered. AI analysis suggests checking:
Based on door/furniture clash detected, high probability of additional conflicts in:
Door schedule vs plan discrepancy detected. AI suggests verifying:
Most Part M requirements are well-specified. Only 2 minor issues found:
Browse through all detected issues above. Use filters to focus on Critical/High priority items first.
Each issue has a "Copy to Clipboard" button. Click it to copy the ready-to-use specification text.
Paste the specification into your Revit/AutoCAD drawings and make the necessary updates.
Come back here and click the status button to mark the issue as "In Progress" or "Resolved".
Invite team members to collaborate. Status updates and comments sync in real time across your whole studio.
Join architects saving 4+ hours per review while protecting their projects from costly construction rework.